Use
The LGB... burner controls are used for
the startup and supervision of single- or
2-stage gas or gas / oil burners in
intermittent operation.
Depending on the type of burner control
used, the flame is supervised either by
an ionization probe, a blue-flame
detector QRC1... for forced draft gas /
oil burners, or a
UV detector QRA... (with auxiliary unit
AGQ1...A27).
In connection with the respective
adapters, the LGB... burner controls
replace their predecessor types LFI7...
and LFM1... .
- Automatic forced draft burners for
gaseous fuels to EN 676
- Gas burner controls to EN 298
- Undervoltage detection
- Air pressure supervision with
functional check of the air pressure
monitor during startup and operation
- Electrical remote reset facility
- LGB41... for use with atmospheric gas
burners